Yam paub

Kev tshuaj xyuas kev ceev faj thaum txhim kho thiab kho lub tshuab nqus tsev vacuum breakers

Jan 04, 2024 Tso lus

High-voltage lub tshuab nqus tsev Circuit Court breakers muaj qhov zoo ntawm qhov zoo arc extinguishing yam ntxwv, haum rau kev ua haujlwm tsis tu ncua, thiab kev txij nkawm ntev. Lawv tau siv dav hauv kuv lub teb chaws kev lag luam hluav taws xob, kev hloov hluav taws xob hauv nroog thiab nyob deb nroog, kev lag luam tshuaj lom neeg, metallurgy, railway electrification, mining thiab lwm yam lag luam, thiab tau siv dav. Universally pom zoo xyuas los ntawm kev siv department.

Qhov kom zoo dua ntawm kev siv lub tshuab nqus tsev twj tso kua mis feem ntau yog hais txog lub tshuab nqus tsev arc extinguishing chamber, tab sis nws lub voj voog tu ncua ntev tsis txhais tau tias tsis muaj kev saib xyuas thiab tsis muaj kev saib xyuas. Rau lub tshuab nqus tsev vacuum breaker tag nrho, lub tshuab nqus tsev cuam tshuam tsuas yog ib feem, xws li kev khiav hauj lwm mechanism, kis mechanism, rwb thaiv tsev qhov chaw, thiab lwm yam., uas tseem yog ib qho tseem ceeb ib feem los xyuas kom meej cov kev ua tau zoo ntawm lub tshuab nqus tsev Circuit Court breaker. Ib txwm saib xyuas ntawm txhua yam yog qhov tsim nyog kom ua tiav kev siv lub tshuab nqus tsev vacuum breaker.

1. Kev teeb tsa ntawm lub tshuab nqus tsev Circuit Court breaker

Thaum cov chaw tsim khoom ntawm lub tshuab nqus tsev vacuum breaker tsis ua raws li kev cog lus, nws yog ib qho tsim nyog yuav tsum tau ua cov kev soj ntsuam niaj hnub ntawm qhov chaw thiab tsis txhob muaj qhov muag tsis pom kev ntseeg tus kheej kom ntau li ntau tau.

(1) Ua ntej kev teeb tsa, lub tshuab nqus tsev hluav taws xob yuav tsum tau kuaj xyuas sab nraud thiab sab hauv. Lub tshuab nqus tsev cuam tshuam, qhov chaw thiab cov khoom siv yuav tsum ua kom tiav, tsim nyog, tsis muaj kev puas tsuaj thiab tsis muaj cov khoom txawv teb chaws;

(2) Ua tib zoo ua raws li cov cai ntawm cov txheej txheem kev teeb tsa, thiab cov kev qhia tshwj xeeb ntawm cov fasteners rau txhua qhov kev teeb tsa yuav tsum raug xaiv raws li cov kev cai tsim;

(3) Tshawb xyuas qhov kev ncua deb ntawm cov ncej, thiab qhov kev ncua deb ntawm lub qhov hluav taws xob sab sauv thiab sab qis yuav tsum ua raws li cov kev cai lij choj uas cuam tshuam txog kev tshaj lij thiab kev ua haujlwm;

(4) Cov cuab yeej siv yuav tsum huv thiab ua tau raws li qhov yuav tsum tau ua. Thaum zawm screws ze ntawm lub arc extinguishing chamber, adjustable wrenches tsis raug tso cai;

(5) Txhua qhov rotating thiab zawv zawg qhov yuav tsum tau txav mus los ywj siab, thiab lubricating roj yuav tsum tau siv rau qhov kev sib txhuam txav;

(6) Tom qab tag nrho cov installation thiab debugging yog tsim nyog, nws yuav tsum tau muab ntxuav thiab so kom huv si. Qhov kev sib txuas kho tau ntawm txhua qhov yuav tsum tau cim nrog cov xim liab, thiab lub qhov hluav taws xob txuas hluav taws xob yuav tsum tau smeared nrog cov roj tiv thaiv corrosion.

 

2. Kev hloov kho cov yam ntxwv ntawm lub tshuab nqus tsev Circuit Court breaker thaum siv

Feem ntau, thaum lub tshuab nqus tsev vacuum breaker yog debugged los ntawm lub Hoobkas, nws cov khoom siv kho tshuab xws li qhib qhov deb, mob stroke, tiv tauj stroke, peb-theem synchronization, qhib thiab kaw lub sijhawm, ceev, thiab lwm yam. yog qhov debugged tag, thiab cov ntaub ntawv debugging txuas nrog. . Feem ntau, thaum siv, tsuas yog peb-theem synchronization, qhib thiab kaw nrawm thiab kaw bounce yuav tsum tau kho me ntsis ntawm qhov chaw, thiab tom qab ntawd cov kev ua haujlwm tau ua tiav.

 

(1) Kev hloov kho rau peb theem hauv tib lub sijhawm:

Rau cov theem nrog qhov sib txawv loj tshaj plaws hauv kev kaw thiab qhib qhov nrug thaum lub sijhawm kuaj, yog tias tus ncej kaw sai dhau lossis lig dhau lawm, me ntsis nce lossis txo qhov qhib qhov nrug ntawm tus ncej. Tsuas yog kho qhov qhib qhov ncua deb ntawm tus ncej lub rwb thaiv tsev khi pas nrig. Los ntawm screwing lub union nyob rau hauv los yog tawm ib nrab ib tug tig, nws feem ntau yuav tau kho kom lub kaw thiab qhib tawm ntawm theem nyob rau hauv 1 hli, yog li tau txais zoo tagnrho synchronization parameter qhov zoo tshaj qhov tseem ceeb.

(2) Kev kho qhov kaw thiab qhib ceev:

Qhov ceev ntawm kev kaw thiab qhib yog cuam tshuam los ntawm ntau yam, thiab tsuas yog qhov chaw uas tuaj yeem hloov kho ntawm qhov chaw siv yog lub caij nplooj ntoos hlav qhib thiab tiv thaiv kab mob. Qhov nruj ntawm lub caij nplooj ntoos hlav qhib muaj qhov cuam tshuam ncaj qha rau qhov kaw thiab qhib nrawm, thaum lub sijhawm sib cuag stroke (xa mus rau qhov compression npaum li cas ntawm kev sib cuag lub caij nplooj ntoos hlav) tsuas muaj kev cuam tshuam loj rau qhov qhib ceev. Yog tias qhov ceev ceev yog qhov siab thiab qhov qhib ceev yog tsawg, qhov kev sib cuag stroke tuaj yeem nce me ntsis los yog qhib lub caij nplooj ntoos hlav tuaj yeem nruj; txwv tsis pub, nws tuaj yeem raug loosened. Yog tias qhov kev kaw nrawm yog qhov tsim nyog tab sis qhov qhib ceev qis, tag nrho cov hlab ntsha tuaj yeem hloov kho kom nws nce los ntawm {{0}}.1 txog 0.2mm. Lub sijhawm no, kev sib tiv tauj ntawm txhua theem tau nce los ntawm 0.1 txog 0.2mm. Qhov qhib ceev kuj yuav nce; conversely, thaum qhib ceev heev, qhov kev sib cuag stroke kuj yuav raug kho me me los ntawm 0.1 ~ 0.2mm, thiab qhov qhib ceev kuj yuav txo.

Tom qab ua tiav qhov kev hloov pauv ntawm peb-theem synchronization thiab kaw thiab qhib nrawm, nco ntsoov rov ntsuas thiab kho qhov kev ncua deb thiab kev sib cuag ntawm txhua tus ncej, thiab ua raws li cov kev cai cuam tshuam rau lub tshuab nqus tsev Circuit Court breaker khoom.

(3) Tshem tawm qhov kaw bounce:

Nqus Circuit Court breakers feem ntau muaj teeb meem ntawm kev sib cuag bounce thaum lub sijhawm kaw. Tshawb xyuas cov laj thawj tseem ceeb: ua ntej, qhov cuam tshuam kaw qhov rigidity loj dhau, ua rau kev sib cuag txav tau rov qab axially; Thib ob, lub pas nrig txav txav tsis zoo coj thiab co ntau dhau; thib peb, qhov sib txawv ntawm qhov sib txuas sib txuas yog loj heev; thib plaub, lub dav hlau sib cuag Nws yog tshwm sim los ntawm qhov tsis zoo perpendicularity rau lub hauv paus axis thiab lateral zawv zawg thaum sib tsoo.

 

Rau cov khoom uas twb tau tsim lawm, cov txheej txheem rigidity ntawm tag nrho cov tshuab yog ib tug foregone xaus thiab feem ntau tsis tuaj yeem hloov ntawm qhov chaw. Rau kev taw qhia tsis zoo ntawm kev txav mus los ntawm tus pas nrig, nyob rau hauv cov qauv coaxial, kev sib cuag compression caij nplooj ntoos hlav thiab cov pas nrig conductive txuas ncaj qha, tsis muaj qhov nruab nrab kis tau tus mob, yog li tsis muaj qhov sib txawv. Rau lub tshuab nqus tsev vacuum breakers nrog ib tug off-axis qauv, muaj ib tug steering triangular caj npab nruab nrab ntawm lub caij nplooj ntoos hlav tiv tauj thiab txav mus cuag pas nrig, uas yog txuas nrog peb pins. Qhov no tawm peb qhov khoob, uas yog nquag thaws thaum lub sijhawm kaw. Qhov no yog tus yuam sij rau tshem tawm bounce. Nyob rau tib lub sijhawm, kev saib xyuas yuav tsum tau them nyiaj rau kev hloov pauv ntawm qhov sib txawv ntawm qhov pib siab kawg ntawm lub caij nplooj ntoo hlav thiab lub pas nrig conductive, kom qhov sib txuas sib txuas yog compact li sai tau yam tsis muaj qhov tsis sib xws; Yog tias bounce tshwm sim vim qhov tsis zoo ntawm lub arc extinguishing chamber tiv tauj qhov kawg, nws tuaj yeem ua tau Lub arc extinguishing chamber yog ntsia los ntawm rotating 90 degree, 180 degree, thiab 270 degree feem kom pom qhov sib txuam ntawm qhov chaw sab sauv thiab sab qis. Yog tias qhov no ua tsis tau, lub arc extinguishing chamber yuav tsum tau hloov.

Thaum soj ntsuam nrog kaw bounce, nco ntsoov kom nruj tag nrho cov ntsia hlau kom tsis txhob raug cuam tshuam los ntawm kev vibration.

Xa kev nug